New hygienic pressure transmitters are specifically designed to meet the needs of the food and beverage and life sciences industries.
Cerabar M PMC51 and PMP51 are new pressure transmitters from Endress + Hauser, suitable for accurate absolute and gauge pressure measurements in gases, steams or liquids, and for level, volume or mass measurements in liquids.
Standard accuracy is 0.15% with 0.075% accuracy available as an option. Long term stability is 0.1% of URL/year and 0.25% of URL/five years. (URL=upper range limit.)
The Cerabar M transmitters are available with ceramic or metal process isolating diaphragm seals which allow the sensors to work in temperatures up to 752 ºF or pressures up to 6,000 psi.
Outputs include 4-20mA, 4-20mA with HART, Profibus PA and Foundation Fieldbus.
A separate housing option allows the electronics housing with its optional LCD display module to be mounted up to 33 ft from the sensor to avoid problems with vibration, lack of space and high temperature, or if extreme cleaning of the measuring point is required.
In the separate housing version, no special end-user wiring is required. The sensor is delivered with the process connection and a socket. The electronics housing with a socket and a mounting bracket are supplied as separate units. The cable is provided with a socket at both ends. These cable sockets are simply plugged into the housing and the sensor.
A Cerabar M transmitter can be programmed to calculate level, volume and mass in any tank shape by means of a programmable characteristic curve that accounts for level, pressure, density of the medium and gravitation constant. The system can compensate for foam formation, agitators, screen fittings and liquid gases.
The intrinsically safe (Ex ia/IS) transmitters can be used in hazardous areas, including FM/CSA Division 1 installations. Options are available that make the transmitters suitable for gaseous oxygen, hydrogen and ultrapure gas environments, as well as paint shops.
Models include:
• PMP51 has a piezoresistive measuring cell and a metal welded process isolating diaphragm to handle pressures to 6,000 psi.
• PMC51 has a capacitive measuring cell and a ceramic process isolating diaphragm, and provides a metal-free PVDF connection
All versions are compliant with ASME-BPE, have 3A and EHEDG approvals, can be used for process pressure monitoring up to SIL2, and are certified to IEC 61508 Edition 2.0 and IEC 61511 by TÜV NORD.