Showing posts with label Gas. Show all posts
Showing posts with label Gas. Show all posts

Wednesday, 9 September 2026

Mass flowmeter for gases and liquids.

A new Coriolis mass flowmeter, the OPTIMASS 5400, has been introduced by Krohne. It is designed for standard process applications with gases and liquids. The new device provides customers with an optimised balance of performance, reliability and cost efficiency. Suitable for a broad range of industries, including chemical processing, oil and gas, marine, food and beverage, and pharmaceuticals, the instrument addresses a wide variety of flow measurement tasks.

Typical applications include chemical and hydrocarbon flow control, utility measurement and fuel consumption monitoring. Thanks to its compact design, the flowmeter is also particularly well suited for mobile and skid-mounted systems, trucks, rail tankers and portable process installations.

Developed in response to growing demand for competitively priced instrumentation, the OPTIMASS 5400 bridges the gap between entry-level and premium Coriolis meters. In addition to direct measurement of mass flow, density and temperature, it provides valuable information on volume flow, concentration and flow velocity.

The twin semi-bent tube flowmeter delivers high measurement performance across a wide operating range. It handles process temperatures up to +180°C and pressures up to 100 barg, while the sensor housing provides a typical burst case pressure resistance of up to 200 barg, offering an additional layer of protection and enhanced plant safety. The instrument also delivers excellent mass flow and density measurement accuracy, with an optional mass flow accuracy of ±0.1% for flow rates above 10% of nominal flow.

The OPTIMASS 5400 is based on an innovative, modular production and supply system. This enables optimised processes throughout all production stages, significantly reducing the delivery time of the measuring device. KROHNE aims to consistently achieve a delivery time of two weeks for the standard configuration. OPTIMASS 5400 also comes as a lightweight eco-design that requires significantly fewer materials and components than previous generations of Coriolis flowmeters.

OPTIMASS 5400 features Entrained Gas Management (EGM™) technology, enabling stable measurement across a wide range of gas fractions and complex flow conditions. The technology also provides two-phase flow indication and supports monitoring of gas volume fraction in liquids.

Equipped with modular electronics, the flowmeter supports a comprehensive range of communication protocols, including HART® 7, Modbus, FOUNDATION™ Fieldbus, PROFIBUS-PA/DP, PROFINET, PROFINET over Ethernet-APL and EtherNet/IP™. Three configurable 4…20 mA outputs are available, complemented by integrated Bluetooth® connectivity for wireless access.

Built-in OPTICHECK diagnostics continuously monitor both instrument health and application conditions, providing operators with detailed insights into both the instrument and the process, supporting condition-based maintenance and process optimisation. The flowmeter also enables on-site verification without process interruption, helping operators reduce maintenance effort and increase plant availability.

When used in combination with the OPTICHECK Flow mobile app, the OPTIMASS 5400 enables commissioning, monitoring and field verification to be carried out conveniently and securely via Bluetooth. OPTICHECK DTM is also available for remote access from the control room.

Available in both compact and remote versions, the OPTIMASS 5400 can serve as a flange-to-flange replacement for existing OPTIMASS 1000 series installations.


@KROHNE_USA #PAuto #DWN

Friday, 14 August 2026

Automation for Caspian Sea compression project.

Integrated control and safety systems provide process control, safety shutdown, fire and gas detection, and power management.

BP has awarded Emerson a multi-million-dollar contract to deliver automation technologies for the Shah Deniz Compression project off the coast of Azerbaijan (AZ).

“Emerson has served as the main automation contractor for the Shah Deniz development for over a decade, demonstrating how our proven, end-to-end execution model delivers well beyond the initial build,” said Ram Krishnan, chief operating officer of Emerson. “We are pleased to continue our collaboration with BP, deploying advanced systems to enable remote operations and significantly expand the production profile of Shah Deniz.”

Photo: BP
Emerson previously served as the main automation contractor for the Azeri Central East and Shah Deniz Stage 2 developments. Under the new contract, Emerson will provide integrated control and safety systems to enhance production, safety and reliability on the new offshore compression platform.

The $2.9 billion Shah Deniz Compression project, which includes an electrically powered, normally unattended offshore production platform, represents the next stage in developing the Shah Deniz field in the Caspian Sea. Designed to access low-pressure gas reserves and maximise overall recovery, the platform will be equipped with four 11MW compressors and serve as the central compression hub for gas from the Shah Deniz Alpha and Bravo platforms. The facility will operate remotely from BP's onshore Sangachal terminal, located 55 km south of Baku.

Emerson’s integrated solution includes its DeltaV™ Distributed Control System and DeltaV Safety Instrumented System, which provide process control, safety shutdown, fire and gas detection, and power management. Together, these systems deliver real-time visibility and control of critical operations remotely, helping to reduce operating costs, while improving efficiency, safety and platform availability.

Unlike approaches focused solely on upfront capital costs, Emerson optimises across the full project lifecycle, improving schedule predictability, reducing cost and complexity, and accommodating change when it matters most. Cloud engineering services and digital twin technology bring virtual testing, system integration and operator training together in one connected workflow.

The project is expected to enable approximately 50 billion cubic meters of additional gas and around 25 million barrels of condensate production and export. Construction is scheduled to be completed in 2029, with first gas compression expected from the Shah Deniz Alpha platform in 2029 and from the Shah Deniz Bravo platform in 2030.


@EmersonExchange @EMR_Automation @Emerson_News @HHC_Lewis #PAuto #Gas #Azerbaijan

Monday, 15 June 2026

Combustible gas detection capabilities.

Lower explosive limit monitoring over WirelessHART, for greater hazard visibility without added power or signal wiring

The capabilities of Emerson's Rosemount™ 928 Wireless Gas Monitor have been expanded by adding combustible gas detection, enabling percent lower explosive limit (%LEL) monitoring over the secure WirelessHART® platform. The update helps users monitor combustible hazards in remote or hard‑to‑wire locations without the need for additional power or costly signal wiring.

“Adding combustible gas detection to the Rosemount 928 gives customers more flexibility as safety requirements evolve,” said Dave Ruhland, global flame and gas product manager for Emerson’s measurement instrumentation business. “Facilities can extend their wireless gas detection strategy to include combustible hazards on existing WirelessHART platforms – simplifying installation and supporting reliable monitoring in more hard-to-reach areas across their facilities.”

The updated Rosemount 928 device supports measurements from 0% to 100% LEL, which gives users early warning and complete visibility into combustible gas hazards, helping them detect risks sooner and respond more effectively as conditions escalate.

The combustible sensing technology is also designed to help reduce maintenance over time. Because the sensor does not rely on consumable elements, such as catalytic beads, that can degrade with repeated gas exposure, it can support longer service intervals and reduce the need for frequent recalibration.

Secure WirelessHART communication transmits combustible gas data in real time, enabling deployment with no added power or signal wiring in hard-to-reach areas. The update is intended to complement existing gas detection programmes by helping teams add monitoring points in locations that may be logistically impractical or too costly to hardwire.


@EmersonExchange  @EMR_Automation @Emerson_News @HHC_Lewis #PAuto #Safety

Thursday, 21 May 2026

Flow computer.

Designed specifically to meet the needs of the liquid hydrocarbon and gas measurement markets worldwide.

The highly versatile SFC3000 flow computer from Ex-i Flow Measurement Ltd,. is capable of measuring the flow rate of liquid hydrocarbons, water and petrochemical gasses as well as making CO2 emission measurements for pollution monitoring and control.

Connected to turbine meters the SCF3000 provides accurate measuring of gas flow in networks simplifying billing for suppliers and can be used to monitor network flow load to ensure reliability of supply and maintain energy supply security. the SCF3000 is flexible measuring system which can be configured to meet a wide range of applications and may be operated in a stand-alone single stream flow measurement system or as part of a highly complex multi-stream system. Simple firmware updates ensure the SCF3000 meets the latest measuring standards.

The SFC3000 can operate in a number of ways, such as a standalone flow computer, a supervisory device or as a component of a complex system. Ex~I Flow offer a private labelling service for the SCF3000 for the convenience of Systems Integrators. Featuring a touch screen VGA display and extensive processing capabilities combined with simple to use controls and unique operating software, The SFC3000 can function as a complete station supervisor integrated into a flow computer housing.

The SFC3000 flow computer is the hub of a flow measurement system and requires a number of peripheral components to take measurements. In its simplest form, a flow measurement system will consist of: An SFC3000 flow computer with 1 I/O option board

  • A flow meter (turbine, ultrasonic, differential pressure or Coriolis)
  • A pressure sensor (HART or 4-20mA)
  • A temperature sensor (Hart, 4-20mA or PT100 Platinum Resistance Thermometer).
Note: pressure and temperature sensors are not needed with a Coriolis flow meter, and additional pressure sensors are required for a differential pressure meter.

Turbine, ultrasonic and Coriolis flow meters can be connected using a pulse input, either as a single or dual pulse train. Alternatively, ultrasonic and Coriolis flow meters can be connected via the RS232/485 serial port available on each of the IO option boards. Additional functionality can be added to a basic system including optional I/O boards. With the addition of a communication board data can be obtained from a gas chromatograph or other sources via the serial or ethernet ports. Flow measurement data can also be passed to other systems, such printers or DCS, via the communication board ports. Logged data can be stored internally or in an optional SD card. A density measurement cell can be connected to a pulse or 4-20mA input.

SFC3000 flow computer key features:

  • Measurement conforming to AGA, ISO, API standards of dry and wet natural gas, hydrocarbon liquids, other gases e.g. nitrogen, other liquids e.g. water.
  • NMi Certificates to: WELMEC 7.2 and 8.8, OIML R117, MID 2014/32/EU
  • Standard Features: standalone flow computing function, flow computing combined with supervisory function, up to 2 G-byte additional memory for Alarm, Audit and Data Logging, optional SD card required.
  • Meter types: pulse generating flow meters, most common ultrasonic flow meters, dp transmitters with orifice or venturi measurements.
  • Configurable Display: system diagrams, Trending and graphical displays, Language options, Interfaces to most types of metering equipment and all popular GC’s, Easy Installation and interfacing
  • Supervisory Features, Alarm/Event/Data Logging and Recording, Printer Report Generation, System Diagram Display, Network Communication, Station Controller Functions, Valve Control and Remote Operation.
  • Maintenance Functions: stream summation, pid/sampler functions, flow computer specification.

The SFC3000 is packaged in an industry Standard Half Width 3U High 19” rack construction suitable for panel or chassis mount. It can accommodate up to 6 user plug-in cards and up to five measurement streams in the same chassis. Operating temperature ranges; PRT Inputs, -10°C to 55°C (15°F to 130°F), Hart® and 4-20mA Inputs -25°C to 55°C (-15°F to 130°F). Operating humidity to 90% non-condensing and meets environmental classes M2/E2.


@ExiFlow @proactivefleet #PAuto 

Thursday, 26 February 2026

Flow computer.

Designed specifically to meet the needs of the liquid hydrocarbon and gas measurement markets.

Designed specifically to meet the needs of the worldwide liquid hydrocarbon and gas measurement markets The highly versatile SFC3000 flow computer from Ex-i Flow Measurement Ltd,. is capable of measuring the flow rate of liquid hydrocarbons, water and petrochemical gasses as well as making Co2 emission measurements for pollution monitoring and control. Connected to turbine meters the SCF3000 provides accurate measuring of gas flow in networks simplifying billing for suppliers and can be used to monitor network flow load to ensure reliability of supply and maintain energy supply security.

The SCF3000 is flexible measuring system which can be configured to meet a wide range of applications and may be operated in a stand-alone single stream flow measurement system or as part of a highly complex multi-stream system. Simple firmware updates ensure the SCF3000 meets the latest measuring standards.

It can operate in a number of ways, such as a standalone flow computer, a supervisory device or as a component of a complex system. Ex~I Flow offer a private labelling service for the SCF3000 for the convenience of Systems Integrators.

Featuring a touch screen VGA display and extensive processing capabilities combined with simple to use controls and unique operating software, The SFC3000 can function as a complete station supervisor integrated into a flow computer housing.

The SFC3000 flow computer is the hub of a flow measurement system and requires a number of peripheral components to take measurements. In its simplest form, a flow measurement system will consist of:

  • An SFC3000 flow computer with 1 I/O option board
  • A flow meter (turbine, ultrasonic, differential pressure or Coriolis)
  • A pressure sensor (HART or 4-20mA)
  • A temperature sensor (Hart, 4-20mA or PT100 Platinum Resistance Thermometer).

It should be noted that pressure and temperature sensors are not needed with a Coriolis flow meter, and additional pressure sensors are required for a differential pressure meter.

Turbine, ultrasonic and Coriolis flow meters can be connected using a pulse input, either as a single or dual pulse train. Alternatively, ultrasonic and Coriolis flow meters can be connected via the RS232/485 serial port available on each of the IO option boards. Additional functionality can be added to a basic system including optional I/O boards. With the addition of a communication board data can be obtained from a gas chromatograph or other sources via the serial or ethernet ports. Flow measurement data can also be passed to other systems, such printers or DCS, via the communication board ports. Logged data can be stored internally or in an optional SD card. A density measurement cell can be connected to a pulse or 4-20mA input.

SFC3000 flow computer key features:

  • Measurement conforming to AGA, ISO, API standards of dry and wet natural gas, hydrocarbon liquids, other gases e.g. nitrogen, other liquids e.g. water.
  • NMi Certificates to: WELMEC 7.2 and 8.8, OIML R117, MID 2014/32/EU
  • Standard Features: standalone flow computing function, flow computing combined with supervisory function, up to 2 G-byte additional memory for Alarm, Audit and Data Logging, optional SD card required.
  • Meter types: pulse generating flow meters, most common ultrasonic flow meters, dp transmitters with orifice or venturi measurements.
  • Configurable Display: system diagrams, Trending and graphical displays, Language options, Interfaces to most types of metering equipment and all popular GC’s, Easy Installation and interfacing
  • Supervisory Features, Alarm/Event/Data Logging and Recording, Printer Report Generation, System Diagram Display, Network Communication, Station Controller Functions, Valve Control and Remote Operation.
  • Maintenance Functions: stream summation, pid/sampler functions, flow computer specification.

The unit is packaged in an industry Standard Half Width 3U High 19” rack construction suitable for panel or chassis mount. It can accommodate up to 6 user plug-in cards and up to five measurement streams in the same chassis. Operating temperature ranges; PRT Inputs, -10?C to 55?C (15?F to 130?F), Hart? and 4-20mA Inputs -25?C to 55?C (-15?F to 130?F). Operating humidity to 90% non-condensing and meets environmental classes M2/E2. As leading flow computer manufacturers, Ex-i Flow Measurement specialises in researching, developing and manufacturing products for the gas and liquid measurement industry, with a focus on continuous project development and enhancement. EX-i offer customers market leading performance, quality, reliability, cost and response.


@ExiFlow @proactivefleet #PAuto

Monday, 16 February 2026

Analyser combines laser and paramagnetic detection methods.

Improved regulatory compliance and emissions control.

The Rosemount™ QX1000 Continuous Gas Analyzer, ideally suited for use in continuous emissions monitoring systems (CEMS), but also a good fit in many other types of applications has been released by Emerson. The QX1000 uses paramagnetic detection for O₂ and quantum cascade laser direct absorption spectroscopy for all other gases to meet stringent performance requirements. This integration of different technologies and a modular approach provide a flexible, single-system solution tailored to diverse application needs. The QX1000’s robust design with low maintenance requirements also reduces lifecycle cost and downtime.

The QX1000 uses cold/dry technology, with a sample conditioning system transporting gas extracted from the process to the analyser through a thermoelectric chiller to reduce the temperature to about 4 degrees Celsius (39 Fahrenheit), so most moisture condenses and drops out. Users can easily integrate the QX1000 into existing plant infrastructure, or it can be provided as part of an integrated Emerson system solution, including the sample conditioning system.

“A major differentiator of the QX1000 is the integration of multiple advanced technologies within a single device, providing the best-fit solution for each measurement need,” said Beth Livingstone, global product manager, process gas, Emerson. “The QX1000 is not only the first of its kind, but it also marks the beginning of a portfolio of analysers designed to set new gas analysis standards.”

Measurements made by the QX1000 are ideal for CEMS applications due to the analyser’s high selectivity and accuracy. CEMS are required at most sites with a stack emitting gases to atmosphere, and they are widely used in chemical, oil and gas, power generation, pulp and paper, refining, water/wastewater and other industries.

Leveraging the intrinsic high selectivity of laser-based measurement, this new analyser provides precise monitoring of complex gas streams while delivering continuous, real-time data. Off the shelf, it supports measurement of key regulatory gases, including CO, CO₂, O2, NO, NO₂, and SO₂, with different configurations typically offering detection of one to four gases. Measurement of additional gases, such as CH₄ and N₂O, is also available.

Designed with reliability in mind, the QX1000 eliminates moving parts that are prone to failure and frequent replacement, minimising maintenance and reducing total cost of ownership. Its low-consumable technology is especially critical in the CEMS market, where ongoing operational costs can be a barrier. By reducing system downtime and maintenance needs, the analyser helps end users avoid costly penalties associated with taking systems offline, ensuring continuous compliance with regulatory requirements.


@EmersonExchange @Emerson_News @EMR_Automation @Rosemount_News @HHC_Lewis #PAuto



Tuesday, 9 December 2025

Gas analysers not for Christmas.

James Clements, MD at Signal Group, explains how businesses can extract maximum value from an investment in gas analysis. Using total organic carbon (TOC) measurements at thermal processes as an example, he will argue that the same analysers can also be utilised for process control and for checking the performance of abatement equipment.

James Clements, Signal Group
Just as a puppy is not just for Christmas, a gas analyser is not just for regulatory compliance. Process managers generally install a continuous emissions monitoring system (CEMS) because they have to, by law.

Background.
By the time a CEMS measures a process stream for compliance, the process work is done, and the analysers are simply providing proof that the process is complying with its permit. However, the efficiency with which that compliance is achieved can be substantially improved by monitoring at earlier stages in the process stream. This principle applies to almost all regulated processes with emissions to air, and for a variety of measurement parameters. For the purposes of this article we will take a closer look at thermal oxidation processes such as VOC abatement and incineration.

Incineration is a widely adopted method for dealing with materials such as municipal waste, sewage sludge, clinical and hazardous waste, and animal by-products. The advantages of incineration over other waste disposal methods include significant volume reduction, hazardous material neutralization and energy recovery. However, the process of incineration converts much of the solid waste into gases, so tight regulatory limits apply to air emissions.

Under the Industrial Emissions Directive (IED) incinerators are normally required to continuously monitor emissions of carbon monoxide (CO), hydrogen chloride (HCl), hydrogen fluoride (HF,) nitrogen oxides (NOx), sulphur dioxide (SO2), total organic carbon (TOC) and total particulate matter. Under certain circumstances, continuous monitoring of HCl, HF and SO2 may not be required, and periodic monitoring may be applicable. The specific requirements for continuous or periodic monitoring are detailed in a site’s EPR (Environmental Permitting Regulations) permit. The permit also specifies periodic monitoring frequencies for dioxins and furans, dioxin-like PCBs (polychlorinated biphenyls), heavy metals and poly aromatic hydrocarbons (PAHs).

Following the withdrawal of the Britain from the EU (BREXIT), the requirements of the IED have been maintained in British law through the Environmental Permitting Regulations.

Seeking to minimise the impact of pollution on people’s health and the environment by reducing harmful industrial and intensive livestock emissions across the EU, the revised Industrial and Livestock Rearing Emissions Directive (Directive 2010/75/EU or ‘IED 2.0’) entered into force on 4 August 2024. A key feature of IED 2.0 is the mandate for national authorities to set Emissions Limit Values (ELVs) at the "strictest achievable" level within the BAT-AEL range for a specific installation, unless the operator demonstrates that this is disproportionately costly. As a consequence, ELVs will become tighter.

Thermal oxidation.
Incinerators employ high temperatures to break down complex organic chemicals into simpler forms - ideally water and carbon dioxide. The measurement of TOC emissions is necessary, not just to demonstrate compliance with the site’s permit, but also to help to identify incomplete combustion, which reduces efficiency and increases the risk of non-compliance. The incomplete combustion of some materials, such as plastics, can also result in the production of toxic gases, which emphasises the need for monitoring and feedback control.

Nitrogen oxides (NOx) are worthy of mention in this context because nitrogen and oxygen are abundant in air but do not react in ambient conditions. At higher temperatures, the gases react to form nitrogen oxide (NO) and nitrogen dioxide (NO2), which have serious health and environmental effects, and are therefore tightly regulated. There is a direct connection between combustion process temperature and NOx emissions, so Signal supplies NOx analysers to inform process control. Offering higher levels of accuracy, Chemiluminescence is the preferred measurement method for development engineers at manufacturer laboratories working on new technologies to reduce NOx emissions in the combustion of fossil fuels. For regulatory compliance monitoring, NDIR (Non-Dispersive Infrared) is less costly and more commonly employed.

Process managers seek to avoid incomplete combustion by optimising temperature, residence time and the air/fuel mixture. This process is informed by the continuous measurement of parameters such as oxygen, carbon monoxide and VOCs.

VOC abatement
Thermal oxidation is generally more effective at higher temperatures and with longer residency times, but both of these involve a higher energy requirement, increasing costs and reducing sustainability in the face of rising climate concerns.

In a catalytic combustion system, VOCs are decomposed by thermal oxidization at lower combustion temperatures, which reduces the amount of auxiliary fuel required and can reduce NOx generation. However, there is a risk that the efficacy of the catalyst may be lost due to catalytic poisoning.

VOC monitoring before and after abatement is essential for the optimization of abatement efficiency, and for the rapid detection of potential problems.

Multiplexed gas analysers.
Signal’s extractive gas analysers can be multiplexed, which means that they can be connected to a multipoint sampling system so that one gas analyser can sequentially take measurements from multiple points – before and after abatement for example. To achieve this, Signal has developed a range of ancillary equipment to facilitate sampling from multiple points. For example, Signal's Model 362 splits a single heated sample line into two filtered streams, allowing for parallel analysis of two different sample points. It includes a heated pump, gas distribution manifold, and multiple outputs, including one for a cooler/dryer. This facility to use one analyser for multiple sample points dramatically lowers the cost per measurement location.

Signal MCERTS approved 363SM heated pre-filter
with heated line
Monitoring technology.
Process managers are of course free to select the most appropriate gas analysis technique for process control, but where data are required for compliance purposes, it is likely that a certified standard reference method gas analyser is deployed. For example, the standard reference method for the measurement of TOC is flame ionisation detection (FID).

Signal’s latest FID, the SOLAR CEMNEX, recently passed a rigorous program of tests at TÜV in Germany. As a consequence, this monitor has MCERTS approval verifying compliance with the performance and uncertainty requirements specified in the UK’s Environment Agency Guidance: MCERTS for stack emissions monitoring equipment at industrial installations - Continuous emissions monitoring systems (CEMS) Updated 28 August 2024, EN 15267-1:2023, EN15267-2:2023, EN 15267-3:2007 and QAL 1 as defined in EN 14181: 2014.

Summary.
Process managers know and understand the measurement parameters that can help them to optimise their processes, but they may not be fully aware of the most effective and cost-efficient ways to implement a monitoring system. With over 40 years of experience in designing gas analysis systems, Signal’s in-house experts are able to provide help and advice in the key issues. These include:

  • Measurement technique
  • Sampling points and sample conditioning
  • Multiplexing
  • Calibration
  • Communication, including Wi-Fi & web-enabled


@GasAnalysers @_Enviro_News #Packaging #PAuto #Manufacturing #Mcerts

Friday, 5 December 2025

Flexible gas lock.

Modern cryogenic containers are true masters of insulation. The secret lies in the highly complex double-wall technology, specifically designed for the storage and transport of cryogenic, liquefied gases such as nitrogen, oxygen, argon, or helium.

To reduce heat input to an absolute minimum, a high technical vacuum is created between the inner and outer containers, ideally in the range of 0.05 to 0.001 mbar. However, the challenge lies not only in creating this vacuum but also in maintaining it for years with minimal maintenance. This is precisely where JAKOB's innovative gas lock comes in.

Unlike a permanently installed vacuum valve, this solution offers a crucial design advantage: The gas lock can be completely detached from the container after the evacuation process. This prevents damage to the valve during the rigors of daily transport and eliminates potential leak points. Should the insulating vacuum weaken after extended use, the system allows for quick and easy re-evacuation of the insulation. This technology ensures that the cryogenic containers maintain maximum thermal efficiency over the long term.


@PresseBox @UnnGmbh #jakobantriebstechnik #PAuto #Cryogenic

Wednesday, 26 November 2025

Air and gas velocity.

The new AVS701 from E+E Elektronik sets a new standard in air and gas velocity measurement has been developed for demanding industrial applications. Maximum efficiency and process reliability thanks to the highest measurement accuracy, quick installation using accurate sensor positioning with a specially developed alignment tool, and an integrated process gas library are the key features of this sensor.

An optional external pressure sensor enables environment compensation by correcting for ambient pressure fluctuations. The robust thin-film ceramic sensing element with special coating and the stainless-steel probe head deliver highly precise measurement results even under extreme or corrosive conditions, significantly reducing downtime and lifecycle costs.

The optically and technically redesigned air and gas velocity sensor stands out above all for its accuracy and reliability, as well as significantly simplified installation. It is optimised for demanding industrial applications in a measuring range from 0 to 40 m/s and –40 to +140 °C and is suitable for a wide variety of uses – from cleanroom and pharmaceutical applications to process monitoring in 3D printers. Increased process efficiency and sensor installation that is up to 60% quicker make the AVS701 the best choice in its performance class.


#Epulse #PAuto #Maintainence

Friday, 7 November 2025

Advanced automation, electrical and digital solutions in UAE gas facility.

Electrical Control and Monitoring system to increase operational efficiency and safety at terminal.

ABB has been selected to provide advanced automation, electrical and digital solutions for ADNOC’s Ruwais LNG facility, 230 kilometers west of Abu Dhabi in the United Arab Emirates. Once operational it will be the region’s first all-electric LNG plant, using electric-driven motors instead of conventional gas turbines. ABB will provide its microcontroller-based Electrical Control and Monitoring (ECM) system, a module of ABB Ability™ System 800xA® distributed control system to increase operational efficiency and safety at the facility.

Render of the ADNOC Ruwais LNG facility (Source ADNOC)

As part of the contract – awarded by TJN, an engineering, procurement and construction joint venture involving Technip Energies, JGC Corporation and NMDC Group – ABB will supply its ECM system to provide real-time visibility and control of all electrical assets, enabling rapid fault detection, load optimization and power management to be achieved safely and reliably, while reducing downtime.

By using electric motors for its two liquefaction trains, the Ruwais LNG project can support emissions reduction efforts. According to the International Energy Agency (IEA), electrification of existing LNG terminals, and the use of low-emissions electricity to power these, could significantly reduce the greenhouse gas emissions associated with production, by around 60 Mt CO2e a year.

Global LNG supply has grown faster than overall natural gas demand in recent years, with this trend set to continue with the delivery of nearly 300 billion cubic meters of new annual LNG supply capacity between 2025 and 2030.

“Electrification unlocks the full potential of LNG as a transition fuel to support decarbonization efforts and meet growing energy demands by providing reliable, abundant and affordable natural gas around the world,” said Bjarte Pedersen, Senior Vice President IMEA at ABB’s Energy Industries division. “By improving operational efficiency, preventing fault downtime and optimizing distribution, ABB’s ECM system safeguards production and extends asset life and we are pleased to support ADNOC’s Ruwais LNG facility with our integrated solutions.”

As the region’s first all-electric LNG plant, the Ruwais LNG facility stands at the forefront of ADNOC’s digital transformation journey. By integrating ABB’s advanced Electrical Control and Monitoring system with ADNOC’s AI-driven analytics, the facility will benefit from real-time insights, rapid fault detection, and predictive maintenance, maximizing operational efficiency and safety.

Ruwais LNG will have a total export capacity of 9.6mmtpa and will more than double ADNOC Gas’ LNG production output, helping to meet global energy demand increases and support energy security. ADNOC says over a 12-month period, the facility will be able to produce enough LNG to power every home in a city the size of London for more than two years.


@ABBgroupnews @abb_automation @ABBgroupnews @abb_automation #PAuto 

Wednesday, 29 October 2025

Defeating the ‘whack-a-mole’* that is sustainable packaging!

Gas analysers are performing a vital role for packaging manufacturers looking to check the environmental performance of their latest products as they seek new ways to develop sustainable packaging.

Signal Group has seen a particular increase in demand for its continuous VOC measurement instruments in the packaging sector. VOCs (volatile organic compounds) are emitted during the manufacture of many packaging production processes, but these harmful pollutants are tightly regulated so continuous monitoring is necessary. In addition, it would not be possible, for example, to label a recyclable product as more sustainable if it caused an increase in VOC emissions.

“The packaging industry is currently under enormous pressure,” explains Signal MD James Clements. “Firstly, most of the major players have made commitments under their ESG policies to improve the sustainability of their products. They are doing this because their customers demand it, consumers want it, and of course it’s the right thing to do, but sustainability means different things to different people,” he says. “Secondly, new regulations such as the UK’s Extended Producer Responsibility (EPR) and the EU's Packaging and Packaging Waste Regulation (PPWR) are strongly encouraging packaging manufacturers to increase the use of recycled materials and to develop recyclable and reusable products.”

According to a recent McKinsey report: “The global packaging sector continues to be attractive and is expected to grow faster than global GDP. Industry demand for—or at least interest in piloting—sustainable packaging is also rising as a result of pledges by companies across the value chain to reduce material use, increase circularity, and make more use of recycled materials.”

However, as James Clements explains: “It’s not as simple as that. Yes, waste reduction is enormously important, but the development of new packaging products can be a bit like ‘whack-a-mole’ because sustainability objectives also include other important factors such as carbon footprint and environmental emissions.

“Whilst seeking to develop new, more sustainable and recyclable products, packaging companies are also looking to ensure that they do not inadvertently increase their emissions of pollutants such as VOCs, and this where we are seeing a large increase in demand for continuous analysers,” he adds.

VOC Sources.
VOCs are released by a variety of packaging manufacture processes. Plastics, resins, fibres, textiles, elastomers, solvents, pigments, adhesives and many other products can be manufactured from fossil fuels, chemicals, catalysts and recycled materials, but many of the processes by which these materials are transformed into packaging result in VOC emissions. During polymerisation, for example, unreacted monomers and residual catalysts can be released as VOCs. In addition, the chemicals that are added to the polymers can also be volatile and become VOCs, and during processing at high temperatures, polymers can degrade into smaller, volatile compounds, which are also VOCs.

The manufacture of some food packaging involves the application of a plastic membrane (PET, HDPE, LDPE, PP etc.) to cardboard or paper. This is a good example of a process that releases VOCs which have to be abated. Typically, a Regenerative Thermal Oxidizer (RTO) is used to destroy the VOCs and other industrial pollutants in exhaust gases by oxidizing them into harmless substances like carbon dioxide and water vapour. RTO abatement systems have to be controlled by a gas analyser. For example, a Signal FID can take samples from both ends of the RTO to check abatement performance and demonstrate regulatory performance. This can be achieved with two FIDs or with one FID and a switched sampling system.

Monitoring technology.
The standard reference method for the analysis of VOC emissions is by a Flame Ionisation Detector (FID), which for many years has been at the heart of Signal’s VOC analysers. The FID method is specifically designed to detect carbon-hydrogen (C-H) bonds, making it highly selective for VOCs.

Signal manufactures two main types of FID – fixed and portable. The fixed analysers are permanently deployed to measure VOC emissions in one location, and the portable analysers can be used at multiple sites, where discontinuous monitoring is permissible. These are generally sites with lower emissions where periodic measurements suffice.

In many countries, the monitoring of VOCs for regulatory compliance requires certification to specific performance standards. For example, Signal’s latest FID, the SOLAR CEMNEX, recently passed a rigorous program of tests at TÜV in Germany. As a consequence, this monitor has MCERTS approval verifying that it complies with the performance and uncertainty requirements specified in the UK’s Environment Agency Guidance: MCERTS for stack emissions monitoring equipment at industrial installations - Continuous emissions monitoring systems (CEMS) Updated 28 August 2024, EN 15267-1:2023, EN15267-2:2023, EN 15267-3:2007 and QAL 1 as defined in EN 14181: 2014.

Summary.
It is possible to claim that a product is more sustainable if it has a lower carbon footprint, produces less environmentally harmful emissions, uses less energy and/or water, or if it results in less waste. However, if it only achieves one of these admirable goals, it is important to check that it is not doing so at the expense of the others, and that is why packaging manufacturers are using more VOC analysers.


* ‘whack-a-mole’ = situation characterized by a series of futile, Sisyphean tasks, where the successful completion of one just yields another popping up elsewhere.


@GasAnalysers @_Enviro_News #Packaging #OPAuto #Manufacturing #Mcerts 

Tuesday, 29 July 2025

High precision gas analyser.

The next generation of WIKA's GA11 gas analyser has been launched. This enables switchgear operators, manufacturers and maintenance companies to record the quality of SF6 gas and alternative insulating gases. The GA11 provides precise measured values for humidity, gas purity and decomposition products. 

Temperature-compensated sensing technology and intelligent measuring algorithms based on stability criteria ensure maximum accuracy when measuring cleanliness and dew point – a significant improvement on all previous versions. Optional sensing technologies for sulphur dioxide, hydrogen fluoride, hydrogen sulphide and carbon monoxide also offer high accuracy and long-term stability.

The new instrument is suitable for mobile use due to its lighter, more compact design. The weight of the impact-resistant hard case, which is protected against water jets and dust in accordance with IP65, is just 22 kilograms. An integrated nickel-metal hydride (NiMH) rechargeable battery is also an advantage here. Unlike instruments with a lithium-ion rechargeable battery, the GA11 does not fall under the transport restrictions of the International Air Transport Association (IATA). The instrument can be carried on the aircraft as checked baggage – a plus point for international use.

An intuitive user interface and clear menu navigation ensures that all measurement processes are easy to control. All functionalities of the GA11 are available in both rechargeable-battery and mains operation. Last but not least, a closed measuring system reliably prevents emissions into the atmosphere: The measuring gas is either returned to the gas compartment or collected in an external gas recovery bag.


@WIKANews #PAuto #Manufacturing

Tuesday, 8 April 2025

Continual power supply for critical infrastructure.

Reduce the possibility of unplanned outages and help prevent catastrophic transformer failures.


The recent power outage at London’s Heathrow airport resulted from a substation transformer fire, which highlights the importance of the early detection of problems in critically important infrastructure. As demand grows for continuous transformer monitoring, Vaisala has released a new enhanced version of its Optimus™ OPT100 DGA monitor by adding oxygen and nitrogen parameters.

A transformer’s lifetime is determined by the condition of its solid insulation, which can be detrimentally affected by air leaks. The easiest and most robust way to reliably detect such leaks is to continuously measure the Total Gas Pressure (TGP) of all dissolved gases in the transformer’s oil, where oxygen and nitrogen are the dominating components. TGP therefore provides real-time detection – even in the very early phases - of air leaks into a sealed power transformer’s tank. With the benefit of TGP, decision-makers in transformer maintenance learn whether the insulation system of a sealed transformer is exposed to air, which allows them to make informed decisions on actions such as oil degassing or sealing system repair.

The real-time monitoring of fault gases by dissolved gas analysis (DGA) is a well-known and established method for the early detection of quickly evolving faults. However, some processes develop slowly in transformers – oxidation for example, can affect their operational life, usually taking years to show significant effects. Vaisala has therefore developed its DGA monitors to track the key parameters and thereby automate effective transformer condition assessment.

In the past, oxygen measurement failed to detect slow air leaks when active oxidation processes were simultaneously consuming oxygen. However, slow air ingress can be easily detected with increasing TGP because nitrogen, as an inert gas, would not be consumed nor produced in the transformer. The latest version of the OPT100 is therefore able to combine the TGP value with oxygen measurement to determine whether oxygen consumption due to active oxidation is taking place.

With the benefit of TGP and oxygen monitoring data, it becomes possible to weigh the expected lifespan of the transformer against the costs of investigating and repairing the air leak or implementing mitigation measures. Therefore, traditional DGA of fault gases enhanced with TGP and oxygen measurement represents the ideal monitoring concept for the reliable protection of transformers.


@VaisalaGroup @_Enviro_News #Infrastructure #Power

Tuesday, 1 April 2025

New ultra-sonic flowmeter.

Modular design provides versatility and precision for volumetric and mass flow measurement of gases and liquids.

The Flexim FLUXUS® / PIOX® 731 series from Emerson is a new range of non-intrusive, clamp-on, ultrasonic flow meters designed to offer greater flexibility, convenience and availability. The nine models in the 731 series feature high-performance volumetric and mass flow sensing technologies and a robust, functional design, providing accurate and reliable measurements for both liquids and gases, with no process media pressure limitations.

Process manufacturers often need to make permanent or temporary flow measurements in areas where penetration into the process media would be problematic because it would typically require a production interruption, along with high costs and downtime. Although some solutions are available, not many meet the performance requirements for a wide range of demanding industrial applications.

To address these and other issues, the Flexim 731 series provides non-intrusive volumetric or mass flow measurements with no process media pressure limitations, ensuring cost-effective operation and low ownership costs. Modular hardware enables the reduction of assembly time by 20% for faster delivery, and integration with most up-to-date software and hardware is straightforward.

The 731 series provides disturbance correction for enhanced accuracy in challenging conditions, such as disturbed flows. It also provides the Advanced Meter Verification feature to validate meter performance, Wet Gas Correction to ensure accurate gas stream measurements, and the Dynamic Gas Meter feature for precise mass and volume correction.

Various models are available to meet varying application requirements, including:

  • FLUXUS F/G731 GP – General Purpose: Provides flexibility for various applications, and it includes disturbance correction and the Dynamic Gas Meter.
  • FLUXUS H731 HPI: Ideal for pipelines and terminals, provides leak detection and integrity monitoring, along with mass flow and density measurements.
  • PIOX S731: Focused on chemical industries for measuring mass flow, concentration and density measurements.
  • FLUXUS F731 WD Water Flow Meter: Designed for the water and wastewater industries, with non-intrusive temperature measurement.
  • FLUXUS F731 TE: Suitable for energy management and building automation, with dual-channel thermal energy measurement.
  • FLUXUS G731 CA: For monitoring compressed air and technical gases in life sciences and manufacturing industries.
  • FLUXUS G731 ST-LT/HT: Measures low and high-temperature steam for industries such as food & beverage and power generation.

All models include an 84mm wide x 45mm high backlit display with 240 x128 pixel resolution for easy readability, synchronised channel averaging for precise gas measurements, and a wide power supply range of 0-240 volts AC +/-10% at 50-60 Hz or 11-32 volts DC. A USB-C port is provided as a servicing interface for programming and data extraction.

Meeting ATEx (Atmosphéres Explosibles), IECEx (International Electrotechnical Commission System for Certification to Standards Relating to Equipment for Use in Explosive Atmospheres), and EAC (Eurasian Conformity) standards, with FM (Factory Mutual) certification expected in April 2025, the Flexim 731 series is designed for global use and compliance.


@EmersonExchange @Emerson_News @EMR_Automation @HHC_Lewis #PAuto

Wednesday, 5 March 2025

Fast and reliable gas detector.

Simple to set up, install and maintain, with factory calibration that persists throughout its lifecycle.

The Rosemount™ 625IR Fixed Gas Detector has been released by Emerson. This instrument is designed to provide reliable and fast gas detection in all plant environments using advanced optical absorption detection technology.

End users need fast and reliable detection of hydrocarbon gases without false alarms, so gas detectors must be able to operate reliably in hazardous environments and all weather conditions. Installation must be simple, with minimal maintenance required, and long-term reliability is a must.

The Rosemount 625IR Fixed Gas Detector meets these needs by using specialised, solid-state dual IR sources and dual IR receivers, which combine to provide continual cross checks and internal adjustments that maintain the factory calibration. Heaters on the optical surfaces and a range of optical protection accessories provide continual detection without unexpected downtime.

The detector is simple to install and maintain because it remains factory-calibrated for life due to its advanced drift monitoring technology and health monitoring diagnostics. A range of accessories are available to make function testing fast and easy using either test gas or a gas-free test filter, with the latter option greatly reducing maintenance time and cost.

Other accessories are available to simplify installation in various applications, making it possible to use the detector in extractive gas detection applications. Duct-mounted versions are also available in two lengths to provide fast, accurate and representative detection across ducts or voids.

The Rosemount 625IR has a standard operating temperature range of -40 to +75 degrees Celsius (-40 to +167 degrees Fahrenheit), and its ingress protection levels are IP66/67 and NEMA 4X. It is rated for use in hazardous areas, specifically North American Class 1, Division 1, Groups B, C and D, and INMETRO/ATEX/IECEx - Ex db ib IIC T5 Gb, and it is certified for marine applications.

The detector is SIL2 rated in accordance with IEC61508, and SIL3 rated when used in a 1oo2 voting configuration, and has a five-year proof-test interval, which gives end users confidence to significantly reduce the amount of scheduled maintenance visits.


@EmersonExchange @Emerson_News @EMR_Automation @HHC_Lewis #PAuto

Monday, 3 March 2025

Sensors and analysers for production & water monitoring.

The new Process Analytics Catalogue for 2024-25, from Mettler Toledo, provides a comprehensive overview of solutions for analytical measurements in liquid process applications, pure water monitoring and gas-phase measurement. The catalogue provides up-to-date information on equipment for measuring some of the most important analytical parameters in process and water monitoring, and includes some unique innovations, like the 2850Si dual silica and phosphate analyzer.

Ranges include:

  • Sensors & analyzers for pH, ORP,dissolved oxygen,dissolved carbon dioxide, turbidity and conductivity.
  • Water monitoring equipment for total organic carbon, conductivity, dissolved oxygen, dissolved ozone, pH, sodium, silica, chloride, sulfate and bioburden.
  • Gas analyzers for a wide range of process gasses, including oxygen, moisture, methane and ammonia.

The Process Analytics Catalogue includes details on Mettler Toledo's three major solution groups:

– The Ingold business unit focuses on in-line analytical measurement solutions for industrial processes in biotechnology, pharmaceutical, chemical, and food and beverage manufacturing. Analytical parameters of Ingold covered in the Process Analytics Catalogue include pH, redox and ORP, dissolved carbon dioxide (CO2), dissolved oxygen (O2), turbidity and optical density, and conductivity.

– The Thornton business unit is a world leader in pure water analytics. Thornton instrumentation is trusted globally in the pharmaceutical, biotech, power generation and microelectronics sectors. With solutions for pure and ultrapure waters, including USP-regulated waters, the Process Analytics Catalogue provides details on Thornton solutions for measuring conductivity/resistivity, pH, dissolved oxygen (O2), dissolved Ozone (O3), total organic carbon (TOC), sodium, silica, chloride and sulfate, and microbial contamination.

- Solutions for gas analytics, including amperometric sensors and tunable diode laser (TDL) analyzers are included. The unique in situ, probe-type TDL analyzers that are included in the Process Analytics Catalog, measure parameters including oxygen (O2), carbon dioxide (CO2), moisture (H2O), hydrogen sulfide (H2S), hydrogen chloride (HCl), methane (CH4) and ammonia (NH3).

- Also included in the Process Analytics Catalogue is information on Intelligent Sensor Management (ISM®) technology, a digital sensor platform that helps ensure reliable measurements and high measurement uptime via unique predictive diagnostic tools.


Mettler Toledo products are marketed in Ireland through DWN Instrumentation and Mason Technology.

@mettlertoledo @MasonTechnology #DWN #PAuto #Laboratory

Wednesday, 4 December 2024

Simple natural gas analysis in custody transfer etc.

Compact and cost-effective solution for custody transfer, carbon capture and other applications of traditional and non-traditional gases.

The Rosemount™ 470XA Gas Chromatograph, just released by Emerson, is designed to simplify natural gas analysis in custody transfer and other process applications.

As natural gas sources have evolved to include sustainable and renewable sources, such as landfill gas and biogas, the need to provide greater gas chromatograph flexibility has accelerated. Existing designs provide the needed capabilities, but a smaller form factor and a more cost-effective solution is needed.

The Rosemount 470XA addresses these and other needs with an analyzer design based on the versatile and industry-proven Rosemount™ 770XA Gas Chromatograph, known for its robustness and wide variety of applications. This opens a wider range of use cases for a product in this segment, such as for carbon capture utilisation and storage, renewable natural gas, and custom applications.

The 470XA provides the same reliable and accurate C6+ BTU/CV measurement that users have come to expect from decades of traditional Rosemont gas chromatograph technology, but now with the added benefit of being a more economical solution for a wider variety of emerging applications.

A full-colour LCD local operator interface and easy-to-use software reduces the need for specialised training by guiding operators through common operational and maintenance functions. Preinstalled Rosemount MON2020 software simplifies analyser configuration, maintenance, and data collection.

The 470XA doesn’t require a shelter for operation in most environments, lowering total cost of ownership. A fully serviceable module combines all critical functional parts in one assembly, allowing for quick and easy field replacement or repair.


@EmersonExchange @Emerson_News @EMR_Automation @HHC_Lewis #PAuto

Friday, 27 September 2024

Tee-shirts to intrigue!

Intriguingly, the Signal Group stand at AQE 2024 (9/10 October Birmingham GB), will be staffed by gas analysis experts wearing T-shirts saying ‘Ask me about MCERTS!’ It’s too early to say more, but anyone interested in VOC emissions monitoring should head for Stand-L5…if only to try out the detachable tablets.

With a heavy focus on technology development, Signal’s MD James Clements is keen for visitors to see the latest advances in gas analysis equipment. “For many people this will be the first opportunity to see the detachable tablets that now sit where our instrument screens used to be. These tablets are now standard across our entire range, opening up a new world of opportunities, and we look forward to demonstrating them at AQE,” he explains.

“Detachable tablets allow remote operation for safety and convenience, but our Series 4 (S4) instruments also have their own IP address, and are compatible with multiple communications methods, which means that users have secure access to their analysers at any time, from anywhere.”

In addition to the latest technologies, Signal’s stand will also feature some of the company’s gas sampling, handling and calibration equipment, much of which has been well-proven in the field and has not changed for years. “Our Gas Dividers are a good example of great design that has stood the test of time,” James explains. “They have been proven to be highly accurate, and can help reduce the cost and uncertainty that comes with multiple calibration bottles. This will be of interest to both AQE visitors and exhibitors.”

Signal Group experts will be available on the company’s AQE stand to discuss gas analysis issues such as sampling methods, sample treatment, analytical technologies, calibration and remote communications.

Summarising, James says: “Even those visitors that don’t currently need any gas analysis equipment should visit our stand - for the same reason that everyone should test-drive an electric car; everyone should come and play with our removeable tablets.”


@GasAnalysers @_Enviro_News #AQE2024 #AirQuality #PAuto

Thursday, 5 September 2024

Gas density sensor integrates with IIoT systems

The new model GD-20-W gas density sensor from WIKA supports the digitalisation of gas-insulated switchgear. The wireless device with integrated battery and radio module allows for easy integration into IIoT environments.

The sensor communicates the values measured for gas density, temperature and pressure via the LoRaWAN® network protocol. The device also features an alarm function for the three parameters as well as for the battery status that signals, independent of the preset transmission cycle, that a limit value has been reached.

As a compact wireless device, the model GD-20-W is particularly suitable for retrofitting existing installations operated with SF6 gas or alternative insulating gases. The installation and maintenance effort is low. The battery life is over ten years, depending on the measuring and transmission rate.

The sensor calculates gas density from the pressure and temperature values. It measures the pressure at 20 °C with an accuracy of ± 0.2 percent. The device monitors gas density continuously and thus allows demand-driven asset maintenance.


• WIKA products are marketed in Ireland through Instrument Technology.

@WIKANews #PAuto #IIoT

Monday, 19 August 2024

Discharge monitoring ensures risks continually assessed.

The installation of a heavy transformer at an alpine location presented the Swiss company BKW with a number of unusual transport issues. Having overcome these challenges, BKW engineers detected small, but rapidly declining discharges after the transformer had been installed. Under normal circumstances they might have considered returning the transformer to the factory, but given the complexity and cost of doing so, a Vaisala OPT100 Optimus™DGA instrument was fitted to monitor the transformer continuously.

“Our initial tests showed that the transformer was working well,” explains BKW primary engineer Lukas Eggimann. “However, the detection of discharges, no matter how small, represented a potential risk, so the online DGA monitor was fitted to ensure that alerts would be issued if any abnormalities developed within the transformer.”

Alpine transformer challenges.
In response to increasing demand, and to increase the security and resilience of the power supply in the Gstaad region of Switzerland, an additional 75 MVA transformer 220 kV / 50 kV was required. However, the installation site was located high in the Alps with challenging access issues. For example, it would be necessary to climb steep roads and to cross bridges that are not designed for such heavy loads.

Two attached trailers were necessary to carry the transformer, along with a self-propelled vehicle, resulting in a total payload of 123 tonnes, which exceeded the capacity of some bridges. For example, it was not possible to avoid a narrow bridge with a 32-tonne limit, so substantial reinforcement had to be implemented prior to the transformer’s arrival (see photo right).

Ensuring transformer reliability.
Following installation, BKW’s transformers are thoroughly inspected by the company’s in-house diagnostic team, as well as the Technical Commission for High Voltage Issues (FKH). Partial discharges were detected during these assessments, although a strongly decreasing trend was observed over 4 to 5 hours. “There are a number of potential causes of these discharges,” Lukas explains. “For example, tiny fragments of metal could be present as a result of welding activity during manufacture of the compartment, or the discharges might be caused by other factors such as voids, bubbles or moisture. Whatever the reason, the concern is that they might later develop into serious problems resulting in transformer failure.”

The transformer had tested perfectly in the factory, the discharges were reducing rapidly during on-site measurement, and the costs and complexity of returning the transformer to the factory were prohibitive, so, in order to avoid any potential risk, the Vaisala DGA monitor was installed.

Why monitor continuously?
The traditional method for checking the performance status of transformers is to manually collect oil samples once per year for laboratory analysis. This spot sampling method provides an indication of dissolved gases and oil quality at one moment in time. In contrast, continuous DGA monitors are able to detect problems instantaneously – before they become serious. Continuous monitors are also able to reveal trends so that users can correlate gas levels with transformer load, for example.

The Vaisala OPT100 Optimus™ DGA can be installed in less than two hours and with autocalibration and IR reference measurement, the instrument is able to deliver reliable gas trending data. Vacuum gas extraction eliminates fluctuation caused by oil temperature or pressure, and hermetically sealed optics prevent sensor contamination. Moisture and hydrogen are measured directly in the oil with a capacitive thin-film polymer HUMICAP® sensor and solid-state sensors. Importantly, the OPT100 measures the total dissolved gas pressure of the oil and detects any air leaks in sealed transformers without the requirement to monitor oxygen – which can be a misleading measurement.

“The OPT100 is a risk reduction tool,” explains Vaisala’s Andreas Hilgers. “In Gstaad, BKW are using it to ensure that the very slight concerns revealed by the post-installation tests, are mitigated by reliable continuous monitoring. We have some customers that use Vaisala DGA monitors on all of their new transformers, and other users who only install them where, say, the transformer passes FAT tests, but not the site acceptance test.”

The OPT100 can be incorporated into power companies’ SCADA systems, but it is also able to provide secure standalone communications. Lukas says, “This is an important feature for cybersecurity because the addition of an instrument such as this should not provide an additional entry point for hackers.”

The ease of installation was also an attractive feature for Lukas. “Of course, it was good that we were able to install the OPT100 quickly and easily,” he explains. “But the typical lifespan of a transformer is 40 to 60 years, so it is equally important that the monitor can be removed easily at a later stage.”

Performance to-date.
The OPT100 was initially installed in 2022, and since that time both the transformer and the DGA monitor have performed well with no sign of any abnormalities. Good correlation has been shown between the OPT100 measurements and the results from samples taken and tested by FKH, and there have been no indications of increased gas levels in the transformer oil.

The fleet of BKW transformers is in very good condition, and is monitored regularly by offline diagnostics and oil sampling for analysis. If transformers exhibit any abnormalities, the monitoring interval is shortened as a first step, and if concerns remain, the installation of an OPT100 would be considered. “Our risk reduction strategy is therefore to take action when any abnormalities are detected – much like human healthcare,” Lukas says. “Continuous DGA monitors therefore represent an essential tool in our risk management strategy, and the OPT100 has been shown to deliver the reliability and peace of mind that we need – especially when the access road has a 32-tonne limit!”


 @VaisalaGroup@_Enviro_News #PAuto #Switzerland