Saving in steam boiler operation.

There is great potential for savings in terms of costs and resources with heavily fluctuating load and condensate modes in steam boiler operation. This operating style is characterized by a rigid metering operation with constantly open vapors. 

OFS Online Fluid Sensoric offers the possibility to enter several important parameters on their website in order to determine possible savings potential.

Continuous monitoring of pH, residual oxygen and conductivity of the feed water, condensate and boiler water allows the changed conditions as a result of the operating modes to be determined and constantly adapted to new changes. In this way, steam, water and energy can be reduced and service and maintenance simplified.

On the website "steam boiler optimization", comparisons between the fixed and variable operation of the boiler system are explained as well as measures to improve them. By entering operating data for the feed water and steam boiler, the expected savings are displayed online in a clear manner. Of course, these are guide values ​​and should be specifically agreed with the operator taking into account real conditions on site.

Because steam and hot water systems are among the most expensive cost centers in a company. OFS solutions without high investment costs offer the operator the opportunity to save costs on energy, fuel and water. This not only makes boiler operation more economical, but also more ecological and sustainable.

In practice, the feed water boilers are operated with the vapor valve open all the time in order to guarantee freedom from oxygen. However, the presence of oxygen-free water enables the vapor valve to operate more efficiently if these requirements are met. In this way, steam losses are only reduced to the bare minimum. With a qualitative monitoring of the dissolved oxygen content in the feed water and an automatic control of the vapor valve, unnecessary water and energy losses are prevented.

Furthermore, in connection with the dosing control for the oxygen binding agent, ineffective salt build-up in the feed water (theoretically up to 10 mg / l excess) is prevented. The thickening in the steam boiler is consequently improved combined with less desalination. This reduces fuel, treated process water and generated carbon dioxide to the bare minimum.

A pH value of nine to ten in the feed water is quite feasible and legally permissible. However, the consumption of chemicals increases up to 10 times. This results in up to a 10-fold increase in energy and water losses.

If the pH, conductivity and residual oxygen are constantly monitored and controlled, the dosage of inhibitors can be reduced to a necessary minimum. The result is less energy and water losses in the steam boiler. At the same time, the efficiency of the steam boiler operation improves and carbon dioxide emissions are also reduced.

Using the example of the printing service provider Prinovis GmbH & Co. KG at the Dresden location, the goal was set to reduce the use of steam and chemicals. There are three large-capacity water boilers each with five MW and two gas engines with five MW each and a downstream waste heat boiler. Then "FWO-Control" was subsequently installed on the feed water boiler. This monitors the feed water, doses quality-oriented inhibitors and controls the vapor valve on the feed water boiler depending on the oxygen. The measurement and control process resulted in savings of up to 50% due to the adapted addition of chemicals to the feed water boiler. The steam losses from the degassing from the feed water tank could also be reduced by more than 50%, so that the investment amortized within a year.

As a result, increased savings in resources and energy can be demonstrated with the optimized variable operation, which has led to better efficiency of the entire steam boiler system. 

@PresseBox #OFS #PAuto #Germany

Wednesday, 9 December 2020

Mobile water analysis in steam boiler.

Checking relevant parameters in the water from steam boiler systems is easy and reliable with the help of the simple handling and fast response time of the µdox measuring device

The different load modes in steam boiler operation result in over- and under-dosing of chemicals. Preventing this from happening requires exact and quick control measurements on a daily basis. Correct dosing of chemicals prevents corrosion and deposits and supports safe long-term boiler operation. To prevent the risk of corrosion, the dissolved oxygen content must not be greater than 20 µg / l. This can be determined precisely with the oxygen electrode of the µdox handheld measuring device from OFS Online Fluid Sensoric, quickly and precisely.

In addition, the exact pH measurements in feed water and steam boilers in connection with the alkalization are absolutely necessary. The pH electrode from µdox offers a correct determination of the pH value not only in salty, but also in low-salt hot water. The pH sensor can also be used to determine m and p values ​​(acid capacity). All electrodes offer temperature-compensated measurements and simple, fast procedures for precise calibration.

The measurement results from up to eight different measuring points are saved according to date and time. After transferring the measurement results to a connected PC, it is possible to edit and visualize the data. In addition, there is no need for a time-consuming training period in handling the device due to the intuitive operation and the clear display. The robust construction of the measuring case makes its use in industry unproblematic and safe. The “mini-laboratory” is particularly suitable for daily use as a tool for boiler keepers and system operators. Efficient operation of the steam boiler can thus be ensured. In addition to analyzes on hot and steam boiler systems, µdox also enables use in district heating networks and for checking online measurements in power plants.

@PresseBox #OFS #Pauto 

Tuesday, 8 September 2020

Water softner alarm.

If hard water is produced at the output of the softener instead of soft water expected, this may be due to the water softener tank. The concentration of salt or water may be too low or there may be other defects in the tank. A direct message may be monitored indicating that maintenance is required on the salt/brine tank of the softener.

The WLAN-enabled sensor SALIS, developed by Online Fluid Sensoric GmbH (OFS), enables alarms to be received by e-mail. The early identification of the problem allows quick measures to avoid unnecessary hard water damage. To get soft water for more security and at the same time to minimize the effort for controls and maintenance to the bare minimum.

Provided that a WLAN network is available at the location of the water softener and the salt / brine storage tank must be serviced. The operator then receives an e-mail message from the SALIS system, ideally directly on his smartphone. A reminder function can be activated, with which the evaluation unit of the sensor sends an e-mail as a reminder every 24 hours.

If there is no WLAN available at the location, a potential-free contact is available to forward the sensor's alarm by wire. Two LEDs on the device also indicate the status and any alarms on site. This means that you can always be sure of knowing when the maintenance of the water softener tank has to be carried out.

The sensor can be quickly installed in any salt / brine storage tank of the softener. The compact control is space-saving and easy to assemble. The high level of accuracy, quick responsiveness and stability help to quickly identify problems with the softener and to inform the operator.

It is optionally possible to connect and signal another external alarm of the softener. If there is a problem with the control of the water softener, the alarm is forwarded by e-mail or potential-free contact. If necessary, the alarm output time can be parameterized for the sensor and the external device.

SALIS can be used to identify problems with the water softener tank. The water in the tank dissolves part of the salt over a few hours, turning the water into brine. When the softener is exhausted, this brine is required to regenerate the softener. With each regeneration, the salt supply decreases. The humidity in the storage tank causes the salt to incrust and can clog the water pipe in the tank or block the salt in the upper part of the tank. Every water softener therefore requires continuous monitoring of the brine-salt storage system.

SALIS takes on this task of constantly checking the tank. This permanent control prevents water damage and reduces maintenance work to a necessary minimum.